1 Check cable wiring[edit | edit source]
Template:Notice bms For correct displaying the actual value you have to make sure that all cables are connected the right way. Just compare with the drawings. Template:Notice bms
The following connectors are bridged on the MBS measurement tool:
- K to S1.
- I to S2.
2 Programming the device[edit | edit source]
If you simultaneously press Keys 1 and 2 for around 1 second,programming mode opens
Programming mode is denoted in the display by the text “PRG”.
You can now use Key 2 to switch between the following programming menus:
- Current transformer
- Voltage transformer
- Parameter list
If you are in programming mode and have not pressed a key for approximately 60 seconds or simultaneously press Keys 1 and 2 for around 1 second, the UMG96S returns to display mode.
Set up instructions:
| ===Current transformer=== |
|---|
| Template:Image |
| Read the data from the current transducer and enter them here. E.g. 1kA / 5A
|
| ===Voltage transformer=== |
|---|
| Template:Image |
| Only used at 690V supplies.
|
| ===PROFIBUS Address=== |
|---|
| Template:Image |
| Parameter 000, Value <Bus Address>
|
- Quit programming
Simultaneously press both keys for around 1 second.
3 Error Codes[edit | edit source]
Most common errors:
| Error Code | Description |
|---|---|
| 400 | No PROFIBUS communication |
| 500 | No Input Voltage detected |
4 Sporadic measuring problems[edit | edit source]
If you have a lot of harmonics on the mains of your line sometimes the Janitza shows wrong values. This happens on IR heaters on MDO and on Vacon or Siemens drives for main extruders.
To fix this issue set the Parameter 63 on the Janitza to 1 for 50Hz or to 2 for a 60Hz mains.
5 Confirm Power Supply Current and Power[edit | edit source]
Verify the measured current, power, Cosφ
There are possible sources of wrong measurements
- Current coil is connected wrong
- Current L1/2/3 does not correspond to the Voltage L1/2/3
If you have negative cosPhi displayed in PVSS and you wonder why on the Janitza display it only shows positive values note the indication "cap" or "ind".