1 Usage[edit | edit source]
Is used for the presssure mininmum on the winder chucks
2 Parameter Settings[edit | edit source]
| Parameter | BMS Settings (PN3002) | Factory Setting | Description |
| SP1 | 72 | 25% VMR* | Switch-on point |
| rP1 | 70 | 23% VMR* | Switch-off point |
| OU1 | Hno | Hno | Configuration of the switching output |
| OU2 | I | I | Configuration of the analogue output (I / U) |
| Uni | bar | bar | Display unit |
| HI | 100 | 100 | Maximum value memory for the system pressure |
| dS1 | 0.0 | 0.0 | Switch-on delay for output 1 |
| dr1 | 0.0 | 0.0 | Switch-off delay for output 1 |
| dAP | 60 | 60 | Damping |
| diS | d2 | d2 | Setting of the display |
Note: * = the indicated percentage of the final value of the measuring range (VMR) of the corresponding sensor in bar / mbar is set
3 Sensor Types[edit | edit source]
There is a new model Version:
- PN3092: 0-100bar (Pmax = 300bar)
- Adjust it like all the other types with the table above. Sp1 72bar and rsp1 70bar at the winder Chucks.