Public:Generator E27 - Parts and software update

Template:Infobox bms

1 Parts inside the generator[edit | edit source]

Part Ref
Line Filter A1
1Ph_filter_rectifier A2
Halfbridge_1kW_EH A3
ElecHeat A4
Halfbridge_1kW_HV A5
HVsupply A6
Temp-Hum-Sensor A20
Transformer_EH T1
Transformer_HV T2
Cooling fan G1
HV Switch V1
Safety cover switch S1
Door switch S2
DC/DC converter A
Connection terminals B
HV output terminals C
PLC and IO modules D
File:E27 inside generator.png
Inside the generator

2 Software Update by Siemens Automation Tool[edit | edit source]

You will find the Software "Siemens Automation Tool", if not installed yet, here on the Brückner Server \\brueckner.de\sonst\bms_ee_sw\SOFTWARE\Siemens_SIMATIC_Automation_Tool\

Firmware: \\brueckner.de\dept\BMS_EE_EXT\PUBLIC\Firmware\Heinzinger

The software should be installed on the FieldPG (CAE) - if not, it is recommended to install it.

In order to search and find the PLCs you must be in the same network. The search cannot succeed through PN-PN-couplers, you must connect the network "behind" a PN-PN-coupler, so connect the FieldPG on the Heinzinger PLC side of the coupler.

During the update, the PLC will be forced to go into STOP mode, the pinning system must be stopped.

Start Simatic Automation Tool Software.

Select your PG-Interface with the pulldown menu on top. If you get the error message "SIMATIC Automation Tool does not support this device", try to use the option Auto from the pulldown menu.


File:SAT TIA Interface.png

With the button "Scan Network >> Scan entire network" you should see the available PLCs (in Me.Ro case should be only one visible PLC, because we are behind the coupler).

File:SAT TIA ScanButton.png

File:SAT TIA ScanDevices.png

To update the PLC/HMI device software, select the tab "Restore from backup" and select the backup file

File:SAT TIA RestoreBackup.png

Select Restore Device

File:Restore device.png

If you are asked that the PLC will be put to STOP mode, acknowledge.

File:SAT TIA StopDevices.png

A successful backup will be noted in the bottom window:

File:SAT TIA Success.png

Storage Location for the backup files will be found under Options >> Settings >> Backup/Restore. You can also change this path if required.

Run the PLC

File:Run plc.png

Commit the new software to SVN under: _enigineering\public\pinning\heinzinger

When installing Simatic Automation Tool on site - don't forget to put it in EngineeringTools.xls. Remember to switch the PLC back to run after finishing the update.