Public:Fischer DE90 Differential Pressure Transmitter

Template:Infobox bms


Fischer DE90 differntial pressure transmitter is used in a two-channel variant to monitor TDO oven filter pressures.

1 Electrical connection[edit | edit source]

File:FischerDE90Connection.png

1.1 Plug Pin Out[edit | edit source]

File:FischerDE90Plug.png

Use a preassembled 5pin cable Murr Elektronik


1.2 Drawing sample[edit | edit source]

File:FischerDN90drawing.PNG

1.3 Drawing sample 2[edit | edit source]

File:Drawing sample 2025.jpg

2 Configuration[edit | edit source]

2.1 Acess[edit | edit source]

Use default password " 000 " for access.

From the “Measured value display”

File:FischerDE90 Messwertanzeige.jpg
  • Just need to press: 5x ENTER -> UP -> ENTER.
  • Then the login is done and main menu (Level 0) is displayed again to start further configuration.
File:FischerDE90 Hauptmenue.jpg

2.2 Language[edit | edit source]

  • Change Language to English if needed.
  • After login at the main menu (Level 0)
    • go to “Parametrierung” (Level 1) -> “Anzeige” (Level 2) -> “Sprache” (Level 3).
    • Change here to “English” -> the display language will change immediately to English.
  • ->Go “back” to Level 1
File:FischerDE90 Sprache.jpg

2.3 Check settings of the sensor[edit | edit source]

All below settings need to change for Channel 1 & 2 accordingly, if it is a 2-channel-sensor. 

2.3.1 Analog output[edit | edit source]

  • Go back to “Configuration” menu (Level 1)
    • -> Configuratoin -> Analogue output
  • Verify under “An.output 1 type” (and “An.output 2 type” if a 2 channel sensor), if it is set to 4..20mA.
File:FischerDE90 AnalogueOutput.jpg

2.3.2 Measuring Unit[edit | edit source]

File:FischerDN90Unit.PNG

2.3.3 Measuring Range[edit | edit source]

  • Start Value => should be 0
  • End Value => Usually maximum sensor scale
File:FischerDN90Range.PNG

Note the value of measuring end and insert the same at the corresponding WinCC parameter panel under “Factor * ”

File:FischerDE90 Para fac mul.jpg

2.4 Damping[edit | edit source]

  • Without damping, the display is fluctuating extremely.
    • (do channel 1 and 2)
  • After check measuring end
    • -> “Back” -> “Damping C1” => set 1s
  • Path: \Configuration\Channel 1\Measurement C1\Damping C1

(Level: 4)

File:FischerDE90 C1 damping.jpg
File:FischerDE90 C1 damping2.jpg

2.5 Color change of the display[edit | edit source]

  • Green the act value is within range.
  • Red means it is beyond.
  • Here it is important what is set into the WinCC parameter panel (values from ET)
    • For example: in WinCC is set “warning max” or “Alarm max” to 300:
    • “Col.ch. C1 red–grn” -> set approx. 10pa lower than the expected min -> -10 (display is green when line is stopped and not blinking red-grn).
    • “Col.ch. C1 grn–red” -> set the value from WinCC -> 300
  • “Col.ch. C1 hyst” -> set between 5 and 10
File:FischerDE90 C1 ColorChange.jpg
File:FischerDE90 Para WarMin.jpg

Configuration is finished

2.6 Zeropoint calibration[edit | edit source]

This is usually done by the process specialist after dry-run.

File:FischerDN90Zeroing.PNG

2.7 USB-function[edit | edit source]

  • The device has a function to save and load the parameters.
  • With this, it is very easy to configure several devices in short time (like at the TDO annealing zones).
  • Difficult is that the device (of year 2025) just has a micro-USB port and is supporting USB-Sticks just up to 16GB (FAT23 was okay, NTFS was not tested). Hopefully in the future they will put a USB-C port, because is difficult to find an adaptor from micro-USB to USB. Connecting a PC directly is also not working.
  • The mentioned PC software 'inTouch' was also not testes yet. The parameter files can be modified with PsPad, but needs to take care what are you doing there.
File:FischerDE90 USBport.jpg