1 Preparation[edit | edit source]

  • disable the motor in PVSS
  • decouple mechanic connections to prevent damage (remember positions of screws)


2 Identification of motor parameters[edit | edit source]

  • move the piston completely out by pressing the corresponding power contactor
  • note down the Actual Raw value shown in PVSS (= max. raw setpoint)
  • now move the piston completely in
  • again note down the Actual Raw value (= min. raw setpoint)
    • the min. raw setpoint should be smaller than the max. raw setpoint, otherwise check connections of the potentiometer
  • take a look at the motor plate and note down the stroke distance


3 Calculation of PVSS parameters[edit | edit source]

Factor(*) = 1

Factor(/) = (max. raw setpoint - min. raw setpoint) / stroke distance

Offset = min. raw setpoint / Factor(/)

After adding the offset the Actual value has to be 0, multiply the offset with (-1) if necessary.



4 Identification of min./max. setpoints and hysteresis[edit | edit source]

  • set the position hysteresis to 2.0 mm for the beginning


  • take the current Actual value and enter it as new Position 1 Setpoint and Position Minimum Setpoint
  • also enter the value as current setpoint for the motor
  • enable the motor again


  • increase the current setpoint until you reach the desired final position of the piston
  • enter this value as new Position 2 Setpoint and Position Maximum Setpoint


  • increase the positioning hysteresis if the piston is shaking when reaching the end positions

5 Final adjustment[edit | edit source]

Template:Notice bms

5.1 change min/max setpoint[edit | edit source]

File:Elero Junior2 Limitswitch1.png File:Elero Junior2 Limitswitch2.png

For further information refer to http://www.elero-linear.de/viewer/junior1/operating_instructions/flipviewerxpress.html


  • couple the mechanic connections again
  • save PVSS parameters to defaults