TW Temperature Limiter

No categories assignedEdit

Template:Infobox bms

1 Short description[edit | edit source]

The JUMO safetyM TB/TW is a safety device to monitor maximum temperature for different sensors (PT100, PT100, NiCrNi....)

2 Electrical Connection[edit | edit source]

Template:Image

Template:Image

The relais contact 9&10 is closed under normal operating conditions. It is used to directly switch off a heating element.


3 Parameter Setup[edit | edit source]

Enter setup mode & change settings

Press "P" for two seconds and you have entered the first parameter level.

You can adjust AL, VA and DF here.


short description setting
AL alarm value according to your application (e.g. 400°C)
VA warning value set to 0 (see desciption later)
DF digital filter 0.6 (default)

Template:Image

In this first parameter level, press P again for two seconds and you will enter the configuration level.

short description setting
C111 analog input according to your application (001=PT100_3Wire, 040=F-CuNi J, 043=NiCr-Ni K)
C113 decimal place 0 = no decimal point
C114 device function 1 = temp Limiter
C115 switching action 0 = inverse
C116 normal display 1 = measured value
C117 binary input function 1 = like reset key
C118 display switch off 0 = inactive
C119 warning alarm function 2 = interval from the limit value
allo lower limit of the setting range for

limit value AL

-1999
alhi upper limit of the setting range for

limit value AL

9999
offs dMeasurement offset 0
hys1 Limit value switching differential 1
hys2 Warning alarm switching differential 1
C120 Limit-value for relay switching operations 1000
C121 Count for relay switching operations 0
C122 1 hours counter xxx

4 Binary output and relais output function[edit | edit source]

When setting C119 to "2" the warning is coming with a difference towards the alarm value. This difference is the value we set in "VA". If we set VA to "0", the binary ouput and the relais output switch at the same time at an overtemperature event. Unfortunatley the binary output resets itself, while the relais output is still in "bad" position and needs proper reset.

5 Reset Faults[edit | edit source]

Press the reset button with a suitable tool.

There is the option to use the binary input as a reset signal (C117 = 1), but it is okay having to reset the devices manually in case of a real overtemp-event.