Fischer DE90 differntial pressure transmitter is used in a two-channel variant to monitor TDO oven filter pressures.
1 Electrical connection[edit | edit source]
1.1 Plug Pin Out[edit | edit source]
Use a preassembled 5pin cable Murr Elektronik
1.2 Drawing sample[edit | edit source]
1.3 Drawing sample 2[edit | edit source]
2 Configuration[edit | edit source]
2.1 Acess[edit | edit source]
Use default password " 000 " for access.
From the “Measured value display”
- Just need to press: 5x ENTER -> UP -> ENTER.
- Then the login is done and main menu (Level 0) is displayed again to start further configuration.
2.2 Language[edit | edit source]
- Change Language to English if needed.
- After login at the main menu (Level 0)
- go to “Parametrierung” (Level 1) -> “Anzeige” (Level 2) -> “Sprache” (Level 3).
- Change here to “English” -> the display language will change immediately to English.
- ->Go “back” to Level 1
2.3 Check settings of the sensor[edit | edit source]
All below settings need to change for Channel 1 & 2 accordingly, if it is a 2-channel-sensor.
2.3.1 Analog output[edit | edit source]
- Go back to “Configuration” menu (Level 1)
- -> Configuratoin -> Analogue output
- Verify under “An.output 1 type” (and “An.output 2 type” if a 2 channel sensor), if it is set to 4..20mA.
2.3.2 Measuring Unit[edit | edit source]
2.3.3 Measuring Range[edit | edit source]
- Start Value => should be 0
- End Value => Usually maximum sensor scale
Note the value of measuring end and insert the same at the corresponding WinCC parameter panel under “Factor * ”
2.4 Damping[edit | edit source]
- Without damping, the display is fluctuating extremely.
- (do channel 1 and 2)
- After check measuring end
- -> “Back” -> “Damping C1” => set 1s
- Path: \Configuration\Channel 1\Measurement C1\Damping C1
(Level: 4)
2.5 Color change of the display[edit | edit source]
- Green the act value is within range.
- Red means it is beyond.
- Here it is important what is set into the WinCC parameter panel (values from ET)
- For example: in WinCC is set “warning max” or “Alarm max” to 300:
- “Col.ch. C1 red–grn” -> set approx. 10pa lower than the expected min -> -10 (display is green when line is stopped and not blinking red-grn).
- “Col.ch. C1 grn–red” -> set the value from WinCC -> 300
- “Col.ch. C1 hyst” -> set between 5 and 10
Configuration is finished
2.6 Zeropoint calibration[edit | edit source]
This is usually done by the process specialist after dry-run.
2.7 USB-function[edit | edit source]
- The device has a function to save and load the parameters.
- With this, it is very easy to configure several devices in short time (like at the TDO annealing zones).
- Difficult is that the device (of year 2025) just has a micro-USB port and is supporting USB-Sticks just up to 16GB (FAT23 was okay, NTFS was not tested). Hopefully in the future they will put a USB-C port, because is difficult to find an adaptor from micro-USB to USB. Connecting a PC directly is also not working.
- The mentioned PC software 'inTouch' was also not testes yet. The parameter files can be modified with PsPad, but needs to take care what are you doing there.