Template:Infobox bms

1 Overview[edit | edit source]

The E+H Ceraphant T PTC31 is usually mounted on silos and vacuum units. It has a range from 0,1 up to 40bar. It needs three wires.

If everything is ok, the display shows you the pressure and the background lights blue. If the Ceraphant has a problem, it change the background to red and writes an error code on the display.

To connect the Ceraphant with our system, you need a 4-wire card.

2 Checkup[edit | edit source]

Normally, we use the standard configuration on the Ceraphant. If there is any problem, look at the trouble shooting to reset.

3 Configuration in PVSS[edit | edit source]

The picture shows the values, which must be configured in PVSS. According to the nameplate set the parameter in PVSS. In our example 1000 mbar.

Template:Image For PET Lines:

Factor (*) => 400.000
Factor (/) => 27648.000 

For other Lines:

Factor (*) => 1000.000
Factor (/) => 27648.000


4 Function Test[edit | edit source]

You can easily check the Ceraphant by changing the pressure. Compare his local display with the displayed value in PVSS. If this is equal, everything is OK.

5 Trouble Shooting[edit | edit source]

  • If the Ceraphant is dark, check the power-supply.

Template:Image

  • For more configurations, reset and error-codes check the manual