Parameter and settings for the Softstarter of the Basic Pump:

  • Nominal Current Motor: 17A
  • Max. Overload factor (specified by Baratti ): 7
    • Max Current: 17A x 7 = 119A
    • Due to the reason that we can adjust only 5 x In at the Softstarter, we increase the nominal current just on the Softstarter to 24A (24A x 5 = 120A)
  • Class: 10
  • Ramp Up Time: 7 Seconds
  • Voltage Level for Start: 60%
  • Ramp Down Time: 0 Seconds