Sirius 3TK Standstill Monitoring

No categories assignedEdit



Template:Infobox bms

1 Description[edit | edit source]

The Siemens Sirius 3TK2810-0BA02 is used for standstill monitoring at grinder motors. It measures a voltage of the coasting motor induced by remanent magnetization at three terminals of the stator winding. If the induction voltage approaches zero, this means motor standstill for the device and the output relay is activated. The device also detects wire break on inputs L1, L2 , L3.


Template:Image


2 Electrical Connection[edit | edit source]

Template:Image

2.1 Inputs L1, L2, L3[edit | edit source]

coming from motor (detection phases).

2.2 Supply Voltage[edit | edit source]

24VDC on A1, A2.

2.3 Safety Outputs[edit | edit source]

on terminals 23/24 and 33/34 (redundancy for required performance level).

2.4 Control terminals X1, X2, X3[edit | edit source]

X1-X2: Feedback from main contactor (NC contact) enables monitoring function. X2-X3: Must be jumpered to reset wire break fault automatically.

3 Adjustment of Device[edit | edit source]

Template:Image

3.1 Uan[edit | edit source]

Sets the threshold for recognizing motor standstill.

Find out the proper setting by watching the coasting motor (approximately set Uan to 10). The safety outputs must not close if the motor is still turning.

3.2 ts[edit | edit source]

Standstill time: If induced voltage is below threshold Uan, the safety outputs are closed after the standstill time ts (See also state diagram in description). Set ts to three seconds.

4 Status LEDs[edit | edit source]

4.1 DEVICE[edit | edit source]

Lights up green during operation.

Lights up red on internal device faults.

4.2 OUT[edit | edit source]

lights up xellow on EMF > Uan

flashes green when ts elapses

green steady light on enabling the output contacts

4.3 SF[edit | edit source]

flashes on faults in the measurement and feedback circuit and on insufficient auxiliary voltage Uh (see picture below)

Template:Image

5 Further Notes[edit | edit source]

Template:Image

Standstill monitoring only works properly if the STAR-contactor (-K026) of the coasting motor is closed, Otherwise wire break will be detected. Also the NET-contactor (-K025) must be open (NC contacts of contactor connected on control terminals X1-X2).