Parameter and settings for the Softstarter of the Basic Pump:
- Nominal Current Motor: 17A
- Max. Overload factor (specified by Baratti ): 7
- Max Current: 17A x 7 = 119A
- Due to the reason that we can adjust only 5 x In at the Softstarter, we increase the nominal current just on the Softstarter to 24A (24A x 5 = 120A)
- Class: 10
- Ramp Up Time: 7 Seconds
- Voltage Level for Start: 60%
- Ramp Down Time: 0 Seconds