The Siemens AI EnergyMeter module 480VAC/CT HF (6ES7134-6PA00-0CU0) is a compact and easy solution for energy meassurements directly integrated in a ET200SP station. All energy data is processed by the PLC.
S7-software works only if Energymeter is used on a PROFINET-station;
When using a ProfiBUS station the expected amount of values cannot be transferred.
Make sure that Real Power is > 0 and Powerfactor is > 0.7
For this you need to have some consumers running that generate a load.
If Real Power or Powerfactor show implausible values, most likely the wiring is not correct or the load is not high enough.
Powersupplies which supply a grinder might show low power factors. The reason is that the grinder is only running close to its operating point, when material is fed into the grinder. Otherwise it is running with low load. In that case, check the power factor of this supply during the time when the grinder is fed with material. This may also apply to other motors, that are not always running with values close to their operating point.