The Promag 10 is a electromagnetic flowmeter. It is mostly installed at the pipes for water supplies (eg. Cooling Water, Chilled Water).
Please see Public:Energy_Measurement for general instructions for commissioning a flow meter. This article only describes points which are specific to the Promag device.
The measuring range should be at least 20% larger than the expected flow.
The extended measuring range should not be identical to the standard measuring range of the next larger sensor (so that you can immediately see that the measuring range was intentionally extended here and not just by mistake that an incorrect measuring range was entered).
File:Standardrange promag.png Choose a value for the new measuring range that is outside of the standard measuring ranges.
On the device navigate to Current Output -> Value 20mA (see menu structure above)
Go to Endress&Hauser website (www.endress.com), go to menu services and select online serial number search.
Enter serial number and you can identify your Promag flow device and its specific details, including download of instruction manuals and specific technical data.
Access the comissioning via "Home" => "Guidance" => "Comissioning"
Go through the menu and set the marked parameters from the following screenshot (feel free to set additional parameters)