This instruction enables the user to configure the Masterguard UPS


1 Configuration SNMP-Board[edit | edit source]

1.1 Serial Connection (HyperTerminal)[edit | edit source]

Template:Notice bms


  • Enter CONSOLE and confirm with enter key. There is a possibility that the connection isn´t established on the first try, in that case try disconnecting and reconnecting the cable and enter CONSOLE again.
  • User Name: admin
  • Password: admin
  • Press N (Network Configuration)
  • Press T (Toggle/ Dynamic IP Address)
  • Press S (Modify IP Settings)
  • Enter IP-Adress:
  • Enter Subnet Mask: 255.255.255.0
  • Enter Default Gateway: Template:KomIp190 (IPC 3.9) / Template:KomIp71 (IPC 4.0)
  • Change back to the main menu with ESC
  • Press L (Logout/Reboot)
  • Logout with R and reboot SNMP-Board

1.2 Network Connection[edit | edit source]

The serial interface of the communication board is no longer used for commissioning as it is deactivated by default. Setting up the network configuration is directly done over the ethernet port.
The UPS is deliverd together with a CD containing the Masterguard ManageUPS software, which is scanning the network for an uninitialized UPS. As this is sometimes not working properly, an alternative way of setting up the UPS is described below:


By default the ethernet inferface is waiting for an IP assignment over a DHCP server:

  • Download and extract media:Dhcpsrv2.3.zip
  • Connect your notebook directly to the UPS' ethernet interface
  • Change your computer's network settings to a fixed IP (e.g. a free address in the line network)
  • Start the DHCP server wizard (dhcpwiz.exe)
    • Choose your notebook's network interface
    • Set the IP-pool to the UPS' future IP address
    • Save the configuration by clicking the Write INI file button (check overwrite if the file already exists)
  • Tick the Run DHCP server immediately box, Finish and then click the Continue as tray app button
  • Reboot the network interface of the UPS by unplugging/plugging it
  • An info message appears as soon as the UPS is trapped



1.3 Internet Explorer[edit | edit source]

  • Open Internet Explorer
  • Password: admin


1.3.1 TCP/IP Settings[edit | edit source]

Template:Notice bms

  • Open the Administration \ Network Settings page
  • Change the Assign IP Settings dropdown to Manually and click Apply
  • Enter the specific address data into the new fields and save by clicking Apply again
  • The settings will be activated after the next network interface reboot by unplugging/plugging it


Template:Image

1.3.2 Battery Pack[edit | edit source]

Battery Settings

  • Battery Replacement Date: today
  • Ups Battery Capacity Designator: -> 1 (number of batterypacks)

General Settings

  • UPS Name: KomUps

Template:Image

1.3.3 Logging[edit | edit source]

  • Date and Time Settings
  • NTP Settings
    • Adjust Time Zone (same zone as the server)
    • If needed select a Daylight Savings Adjustment
    • NTP Server: Template:KomIp1
  • Update Time Using NTP Now

Template:Image

1.3.4 Event Messaging[edit | edit source]

1.3.4.1 SNMP Traps[edit | edit source]
  • SNMP Trap Designations

Template:Image

1.3.4.2 SNMP Communities[edit | edit source]
  • If a entry exists in Name and Address delete it!

Template:Image

1.3.5 Network Shutdown[edit | edit source]

  • Network Shutdown Controller Settings
    • Network Shutdown Controller Enabled
    • UPS off delay: wait 3 minutes after execution of last group…
    • Cancel UPS Shutdown if Utility Power returns after execution of last group
  • Group 1 Settings
    • Execute after 5 minutes on battery
    • Protocoll: RCCMD
    • IP Address From: Template:KomIp200 To 220
    • Port for Shutdown Sequence: 6003
    • Port for Restart Sequence: 6003
  • Group 2 Settings
    • Execute after 7 minutes on battery
    • Protocoll: RCCMD
    • IP Address from: Template:KomIp1 To 1
    • Port for Shutdown Sequence: 6003
    • Port for Restart Sequence: 6003

Template:Image

1.3.6 Administration[edit | edit source]

1.3.6.1 Security[edit | edit source]
  • Admin User Settings
    • User Name: admin
    • Password: must be generated with Enigma 2000.
  • User Access Settings
    • Web Authorization Options: All Pages except Status Page


Template:Image

1.3.6.2 Network Settings[edit | edit source]

Template:Image

2 Troubleshooting[edit | edit source]

2.1 Fault Reset[edit | edit source]

  • Open Panel for the UPS
  • Show Documents and select the website
  • Press the RESET in the Panel
  • Check in the Menu Logging -> View Logs what the reason was for the fault.


2.2 Serial Connection[edit | edit source]

 PC Com             UPS
 2 ----------------- 2
 3 ----------------- 3
 5 ----------------- 5


2.3 No Messages from the UPS to the Server[edit | edit source]

in /usr/ups/rccmd.cfg, check that all connected IPs are entered

 #
 # RCCMD Configuration (v-2.00.4-1) 
 #
 ListenAddress=Template:KomIp1
 ListenPort=6003
 ListenTimeout=10
 ListenUDP=true
 AllowedAddresses=Template:KomIp180, Template:KomIp182
 AliveAddresses=Template:KomIp180, Template:KomIp182
 AlivePort=5769
 AlivePort=5769
 AliveEnabled=false
 AliveInterval=1800
 AliveRetries=0
 LogfileName=/usr/ups/rccmd.log
 LogfileEnabled=true
 LogfileSize=1024
 ShutdownProg=/usr/ups/rccmd_shutdown.sh
 AliveProg=/usr/ups/rccmd_notalive.sh
 ExecProg=/usr/ups/rccmd_execute.sh
 MsgProg=/usr/ups/rccmd_message.sh
 MailProg=/usr/ups/rccmd_mail.sh
 MsgDatName=/usr/ups/messages.dat


3 First Startup[edit | edit source]

To switch on the UPS first time after delivery could be fail because of an hidden main switch.

The following pictures will explain the proceed to discover the position of the switches.


Now you are able to operate the Main switch.