Simatic Automation Tool

Revision as of 10:53, 9 March 2026 by Max Mustermann (talk | contribs) (1 revision imported)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)


Template:Infobox bms

You will find the Software, if not installed yet, here on the Brückner Server \\brueckner.de\sonst\bms_ee_sw\SOFTWARE\Siemens_SIMATIC_Automation_Tool\

Since Me.Ro and other suppliers are already using Siemens TIA PLCs this Siemens Automation Tool allows us to search the network for compatible PLCs , create a backup and restore it in case of a PLC exchange.

The software should be installed on the FieldPG (CAE) - if not, it is recommended to install it.

In order to search and find the PLCs you must be in the same network. The search cannot succeed through PN-PN-couplers.

Me.Ro PLCs are "behind" a PN-PN-coupler, so connect the FieldPG on the me.ro-side of the coupler.

During the Backup the PLC might be forced to go into STOP mode.So a backup is only to be taken if the line is not in production and there is some time to stop the PLC.

Start Simatic Automation Tool Software.

Select your PG-Interface with the pulldown menu on top. If you get the error message "SIMATIC Automation Tool does not support this device", try to use the option Auto from the pulldown menu.


File:SAT TIA Interface.png

With the button "Scan Network >> Scan entire network" you should see the available PLCs (in Me.Ro case should be only one visible PLC, because we are behind the coupler).

File:SAT TIA ScanButton.png

File:SAT TIA ScanDevices.png

Select the PLC and continue with the button "Backup selected devices".

File:SAT TIA BackupButton.png

To restore a backup to the PLC/HMI, select the tab "Restore from backup" and select the backup file

File:SAT TIA RestoreBackup.png

If you are asked that the PLC will be put to STOP mode, acknowledge.

File:SAT TIA StopDevices.png

A successful backup will be noted in the bottom window:

File:SAT TIA Success.png

Storage Location for the backup files will be found under Options >> Settings >> Backup/Restore. You can also change this path if required.

Create a backup for all Mero PLCs, Heinzinger PLC and Heinzinger touchpanel and commit them to SVN under:

_enigineering\public\corona\mero _enigineering\public\pinning\heinzinger

Name each backup file uniquely e.g. StrPurCorGen001Top (or similar to your datapoint name).

When installing Simatic Automation Tool on site - don't forget to put it in EngineeringTools.xls. Remember to switch the PLC back to run after finishing the update.