1 Liquid Cooling Unit[edit | edit source]

1.1 VEO Heat Exchanger[edit | edit source]

Since the 1830 DAP the Heat exchange units will be delivered with a LOGO. For Parameters and configuration please look inside the manuals.

1.1.1 Dokumentation[edit | edit source]

Flußschematas:

Media:VHEX_40_päivitys_.pdf

Media:VHEX_65_päivitys_.pdf

Commissioning reports:

Media:SD_Card_operation_(ID_370153).pdf

Media:VEO_Heat_Exchanger_(ID_397056).pdf

1.1.2 Communication[edit | edit source]

Vacon OptE9: 172.31.30.20

Logo: 172.31.30.21

Logo TDE (Touchpanel): 172.31.30.25

Set the subnet mask and the gateway exactly like other devices you have on this profinet, e.g. 255.255.0.0 and Gateway 172.31.0.1.

Otherwise you will not be able to ping the two devices from service net.

File:Veo heatex com.PNG

Explanation:

Communication is using SFB14 GET and SFB 15 PUT to communicate directly with a remote PLC (== LOGO).

The local ID for the S7 connection must not be changed without also changing the parameters for the GET/PUT code in SCL. So do not touch or change.

NetPro must be downloaded ! File:VaconLogoNetPro.PNG

1.1.3 Parameter (1829YAP)[edit | edit source]

Temperature Setpoint: 40°C

  • Pressure AI1
    • L: 0.5 bar
    • LL: 0.3 bar
  • Temperature AI3
    • HH: 50°C
    • H: 45°C
    • L: 22°C
  • Flow AI4
    • L: 15%

Template:Notice bms


1.2 HXL-040 / HXL-120 Heat Exchanger[edit | edit source]

The system software and application of the cabinet cooling pump inverter will be kept as delivered ex factory. Only the field bus parameters and temperature setpoints/alarms have to be adjusted.

G 2.11 FIELDBUS
P 2.11.1 1516 Relay output statuses
P 2.11.2 15 Digital input statuses
P 2.11.3 1511 Cooling circuit inlet pressure
P 2.11.4 23 Valve position
P 2.11.5 1500 Cooling circuit temperature setpoint
P 2.11.6 1501 Cooling circuit temperature actual
P 2.11.7 37 Last active fault code
P 2.11.8 - -

The following example is for 35°C setpoint. Calculate setpoint according to humidity curve from manual ( CAUTION: That's minimum setpoints!).

File:Humidity curve.JPG

Manuals: K:\EEC\Berichte Beschreibungen von Prüfungen\2015\Vacon_LC\Dokumentation\

Vacon-NXP-HXL040-Cooling-Unit-Installation-Manual

Vacon-NXP-HXL120-Cooling-Unit-Installation-Manual

Set the monitoring values (low temperature, over temperature alarm and over temperature fault) dependent (-3°C, +3°C, +10°C)

K 3 Keypad Control
P 3.5 PID Reference 40.0
G 2.10 FLOW CTRL
P 2.10.9 OutlTempLowAlarm 37.0
P 2.10.10 OutlTempHigAlarm 43.0
P 2.10.11 OutlTempHigFault 50.0

1.3 Adding Liquid and De-airing[edit | edit source]

Template:Todo

Glycol-Water-Mixture supplied by BMS.