1 Liquid Cooling Unit[edit | edit source]
1.1 VEO Heat Exchanger[edit | edit source]
Since the 1830 DAP the Heat exchange units will be delivered with a LOGO. For Parameters and configuration please look inside the manuals.
1.1.1 Dokumentation[edit | edit source]
Flußschematas:
Commissioning reports:
Media:SD_Card_operation_(ID_370153).pdf
Media:VEO_Heat_Exchanger_(ID_397056).pdf
1.1.2 Communication[edit | edit source]
Vacon OptE9: 172.31.30.20
Logo: 172.31.30.21
Logo TDE (Touchpanel): 172.31.30.25
Set the subnet mask and the gateway exactly like other devices you have on this profinet, e.g. 255.255.0.0 and Gateway 172.31.0.1.
Otherwise you will not be able to ping the two devices from service net.
Explanation:
Communication is using SFB14 GET and SFB 15 PUT to communicate directly with a remote PLC (== LOGO).
The local ID for the S7 connection must not be changed without also changing the parameters for the GET/PUT code in SCL. So do not touch or change.
NetPro must be downloaded ! File:VaconLogoNetPro.PNG
1.1.3 Parameter (1829YAP)[edit | edit source]
Temperature Setpoint: 40°C
- Pressure AI1
- L: 0.5 bar
- LL: 0.3 bar
- Temperature AI3
- HH: 50°C
- H: 45°C
- L: 22°C
- Flow AI4
- L: 15%
1.2 HXL-040 / HXL-120 Heat Exchanger[edit | edit source]
The system software and application of the cabinet cooling pump inverter will be kept as delivered ex factory. Only the field bus parameters and temperature setpoints/alarms have to be adjusted.
| G 2.11 FIELDBUS | |||||
|---|---|---|---|---|---|
| P 2.11.1 | 1516 | Relay output statuses | |||
| P 2.11.2 | 15 | Digital input statuses | |||
| P 2.11.3 | 1511 | Cooling circuit inlet pressure | |||
| P 2.11.4 | 23 | Valve position | |||
| P 2.11.5 | 1500 | Cooling circuit temperature setpoint | |||
| P 2.11.6 | 1501 | Cooling circuit temperature actual | |||
| P 2.11.7 | 37 | Last active fault code | |||
| P 2.11.8 | - | - | |||
The following example is for 35°C setpoint. Calculate setpoint according to humidity curve from manual ( CAUTION: That's minimum setpoints!).
Manuals: K:\EEC\Berichte Beschreibungen von Prüfungen\2015\Vacon_LC\Dokumentation\
Vacon-NXP-HXL040-Cooling-Unit-Installation-Manual
Vacon-NXP-HXL120-Cooling-Unit-Installation-Manual
Set the monitoring values (low temperature, over temperature alarm and over temperature fault) dependent (-3°C, +3°C, +10°C)
| K 3 Keypad Control | |||||
|---|---|---|---|---|---|
| P 3.5 | PID Reference | 40.0 | |||
| G 2.10 FLOW CTRL | |||||
|---|---|---|---|---|---|
| P 2.10.9 | OutlTempLowAlarm | 37.0 | |||
| P 2.10.10 | OutlTempHigAlarm | 43.0 | |||
| P 2.10.11 | OutlTempHigFault | 50.0 | |||
1.3 Adding Liquid and De-airing[edit | edit source]
Glycol-Water-Mixture supplied by BMS.