1 Installer Software[edit | edit source]
You can download the Starter Software free from the Siemens Homepage.
For Example: [[1]]
2 Windows restart message[edit | edit source]
It is possible, that windows is requesting a restart every time the installation is started. In that case if message appears after a restart again, you need to edit the registry.
Delete the key: HKEY_LOCAL_MACHINE/SYSTEM/CurrentControlSet/Control/Session Manager/PendingFileRenameOperations
3 Installation[edit | edit source]
copy and extract all files to a local drive (typically C:) and make sure to have a folder structure similar to the picture below.
- Execute Setup.exe
- Select English for installation language
- Accept license
- Select User-Defined installation
- Select the packages
- Default Settings
- + Simatic CFC is necessary for DCC
- + Simocom U/A for Posmo Drives
- + Drive Monitor for BST/Upgradings
- If there is a previous installation accept the uninstallation.
- Wait for pretty long time (>1,5h) to finish the installation. That's Siemens, they are not in a hurry.
4 Troubles at Starter V4.4 installation[edit | edit source]
There might be a warning at the beginning, ignore it.
4.1 PKZIP[edit | edit source]
If there is a error message while archiving projects, copy the folder C:\Program Files (x86)\PKWARE\PKZIPC to C:\PKWARE\PKZIPC.
5 Accelerate Start up[edit | edit source]
In order to accelerate the slow start up of Starter go to:
Options > Settings... > Workbench
and only select:
- Display "Online/offline comparison" when connecting
- Display "Download motor database to memory card in target device" when connecting (from Starter V5.4)
as shown below:
Template:Image
6 Troubleshooting[edit | edit source]
6.1 Error Message --> The project is write-protected or is already being used by another process on a different computer[edit | edit source]
This message can come up even when you made sure that no other process is accessing the STARTER project. Due to a deinstallation routine of Office365 a problem appeared in combination with STARTER. Because of this all STARTER projects are write-protected.
If that is the case you may have to start a quick installation procedure which takes around 1min. You can find it here [\\brueckner.de\sonst\BMS_EE_SW\SOFTWARE\Siemens_DRIVE-ES_STARTER\Starter_4_5_1_0\InstData\CheckRequirements\Media\setupdir\AceRedist.msi / \\brueckner.de\sonst\BMS_EE_SW\SOFTWARE\Siemens_DRIVE-ES_STARTER\Starter_4_5_1_0\InstData\CheckRequirements\Media\setupdir\AceRedist.msi ]
After that you should be good to go again.