hw>Fkb
No edit summary
 
m 1 revision imported
 
(No difference)

Latest revision as of 10:53, 9 March 2026

Template:Infobox bms

1 General Cable Screen[edit | edit source]

Connect cable screen properly with spring or metal tiewrap to EMV bar
Make sure isolation is dismantled long enough and clip applies pressure

2 Sinamics S120[edit | edit source]

Attach screens of Encoder cables at EMV-bar only!
If this is not done by the switchboard manufacturer, do it on site.
Therefore, make a connection between EMV-bar and backplane with 2 x 16mm2 cables or 2 x high flexibel grounding strap.

Update: do not attach the screens of Encoder cables in the cabinet, the connection through the plug is enough. Refer also to the EMC guideline

File:Cable screen S120.jpg
File:Cable screen S120 2.jpg

3 Sinamics S150[edit | edit source]

File:Cable screen S150.jpg

4 Vacon Drives[edit | edit source]