YM:Schenck ShakeControl VVC29150: Difference between revisions

No categories assignedEdit
hw>Nk
Updated values for Volumetric Discharge Adaption and Linearization Points acording to latest knowledge
 
m 1 revision imported
 
(No difference)

Latest revision as of 10:53, 9 March 2026

Template:Infobox bms

1 Important general information[edit | edit source]

At the end of 2017 the old FRS 0052 controller will be replaced by the new VVC 29150 controller.
As soon as the replacement was done all Vibro Feeders will be equipped with the new Vibro controller.
By taking a closer look at the picture you will see that there are no longer potentiometers like they used to be on the FRS 0052.

Template:Image

As we all know by changing the setting of the potentiometer the oscillation amplitude of the exciter was modified – modifying the oscillation amplitude from now on can only be done via EasyServe anymore.
The parameters of the VVC 29150 can be modified at chapter “42 Virbo Controller VVC” via EasyServe.
The set of parameters consists of 14 settings like P42.07 Gain (Index) 1 and P42.08 Gain (Index) 2 and is saved together with the settings of the dosing unit.
According to Schenck it should not be necessary to modify the default parameters of the VVC 29150, but since we don’t have much experience with the new vibro controller yet we cannot be not sure if it’s going to be like that.
Apart from this, it's important to know, that the new Vibro Feeder also comes with a new vibration sensor named VME 29150-2GD.
This sensor measures the acceleration instead of the velocity which was done by the previous sensor VRS 20300(-1D3G).
Please make sure that you have at least EasyServe v28 installed on your notebook and that Schenck Tersus has the firmware version vlw20172_005.
Disocont® controllers need no firmware update!

2 Software requirements[edit | edit source]

  • PC: EasyServe v28
  • Disocont®: No firmware update required
  • Schenck Tersus:

3 Functionality of the VVC 29150[edit | edit source]

Template:Image

4 VVC 29150 printed circuit board[edit | edit source]

4.1 VVC 29150 screw terminals[edit | edit source]

Template:Image


4.2 VVC 29150 switch[edit | edit source]

If the virbo feeder is equipped with the VRS 20300 sensor set switch S301 to vel. – if the vibro feeder has installed the new VME 29150 acceleration sensor set it to acc.
Set switch S401 to int.

Template:Image


4.3 VVC 29150 slots[edit | edit source]

Set jumper at pin 1 and 2

Template:Image


5 Sensor type[edit | edit source]

Attention: Detection of the sensor is only performed once when the control system's supply is switched on. If the switch S301 was set incorrectly:

  1. Disconnect the VVC 29150 from the 230V power supply
  2. Turn the switch S301
  3. Wait at least 20 seconds before you power on VVC 29150

Template:Notice bms

VRS 20300-1D3G (old)

Template:Image


VME 29150-2GD (new)

Template:Image

6 VAI 20100 analog input card[edit | edit source]

The analog input card VAI 20100 is an expansion board with analog inputs for the VVC 29150.
You only need the analog input card if you want to connect the feed control system Disocont® to the VVC 29150.
Set jumper at 2-3

6.1 Technical data[edit | edit source]

Template:Image

6.2 Installation of the analog input card[edit | edit source]

Therefore please take a look on page 25 of the service manual.

7 VVC 29150 cabling[edit | edit source]

7.1 Connection of VVC 29150 to Disocont Tersus[edit | edit source]

For the connection between a Disocont Tersus and the VVC 29150 a RS485 connection is used.
Only the feed control system DISOCONT Tersus uses the RS485 connection - other feed control systems are connected via an analog connection which means the analog input card VAI 20100 is required.

Template:Image


7.1.1 RS 485 connection between Tersus and VVC 29150[edit | edit source]

Contact on X103 (VVC 29150) Contact on X97 (DISOCONT Tersus)
7 5
8 4






7.1.2 Connection of sensor[edit | edit source]

Attention: Detection of the sensor is only performed once when the control system's supply is switched on. If the switch S301 was set incorrectly:

  1. Disconnect the VVC 29150 from the power supply
  2. Turn the switch S301
  3. Wait at least 20 seconds before you power on VVC 29150


  • Accelerometer VME 29150-2G
Contact on X301 (VVC 29150) Colour of conductor of the sensor cable
1 Black
2 Brown





  • Speed sensor VRS 20300(-1D3G)
Contact on X301 (VVC 29150) Colour of conductor of the sensor cable
1 Blue
2 Red






7.1.3 Connection of exciter and power supply[edit | edit source]

Contact on X801 (VVC 29150) Connecting
1 Exciter
2 Exciter
4 Power supply
5 Power supply









7.1.4 Connection of engineering notebook[edit | edit source]

RS232 connection to perform a firmware update in case the download via Ethernet has failed.

Contact on X102 (VVC 29150) RS232 serial port on the PC
1 (GND) 5 (GND)
2 (Tx) 2 (Rx)
3 (Rx) 3 (Tx)








7.2 Connection of VVC 29150 to Disocont®[edit | edit source]

As already mentioned in chapter 2 you need to have the analog input card VAI 20100 installed at the VVC 29150 in order to run it with the feed control system Disocont®.

Template:Image


7.3 Schenck Unit in Switchboard and long cableing[edit | edit source]

Attention When having the Schenck Units not right next to the Dosing Units but in the +SR21 or in any central Switchboard Romm there are several things requiring special care.
For details check: This links to *Public:Schenck Tersus -> 1.2.1 Schenck Unit in Switchboard and long cableing

8 Parameters of the VVC 29150[edit | edit source]

For detailed information, please take a look in the service manual or at the commissioning chapter below.

P01.16 (Vibro Controller VVC) => Yes

Template:Image

9 Replacement of FRS 0052 by VVC 29150 with Disocont®[edit | edit source]

9.1 Installation[edit | edit source]

  1. Before you start make sure that all control voltages are off
  2. Disconnect all wires from the FRS 0052 – even those which are connected to the grey screw terminals
  3. Set jumper W100 of VAI 20100 analog input card to 2-3
  4. Replace FRS 0052 controller by the VVC 29150
  5. Make sure S301 is set to vel. and S401 to int.
  6. Connect wires (power supply, sensor, exciter, etc.) at the VVC 29150 as follows:

Template:Image

Signal Terminal on FRS 0052 Terminal on VVC 29150
Digital input 1 (starts the feed operation) X2:10 X103:3
Digital input 2 (only relevant if the sensor VRS 20300 is connected) X3:4 X103:4
External reference potential for controlling the digital inputs 1 and 2 X2:6 X103:2
Analog setpoint (+) X2:1 X103:10
Analog setpoint (-) X2:2 X103:9
Digital relay output for feed control system (sends response "Ready" to the feed control system) X2:3 X501:2
Digital relay output for feed control system (sends response "Ready" to the feed control system) X2:5 X501:1
Ground of power supply PE PE
Power supply X1:L X801:5
Power supply X1:N X801:4
Exciter X1:+ X801:1
Exciter X1:- X801:2
Ground of exciter PE Screen clamp
Sensor X4:1 X301:1
Sensor X4:2 X301:2
Ground of sensor X4:3 Screen clamp

9.2 Firmwareupdate of Disocont® Controller[edit | edit source]

No Firmwareupdate required

9.3 Commissioning[edit | edit source]

The commissioning consists of four major steps:

  1. Check actual feeding rate I with current Bypass value
  2. Perform Calibration program “Vol. Discharge Adaption”
  3. Adjust mechanical setup of the Vibro Feeder or modify P42.07 of VVC 29150 if determined Bypass value is too high – recommended range 10-12mA for dosings with low flow rate and 14mA for dosings with high flow rate
  4. Run Calibration programs “Linearization P1, P2, P3 and P4”


9.3.1 Check actual feeding rate with VVC 29150[edit | edit source]

  1. Open EasyServe v28 (or higher) and connect to the dosing unit
  2. Unlock EasyServe user interface
  3. Set P12.21 Bypass Adaption if not already configured to 1,000 and deactivate P12.19 Controller Adaptation
  4. Open "Scale Operation 1" and start Keyboard Mode
  5. Enable Volumetric Mode and start the dosing unit
  6. Set P to Maximum Flow Rate

Template:Notice bms

9.3.2 Calibration program "Vol. Discharge Adaption"[edit | edit source]

  1. View "Scale Operation 1"
  2. Set "Gravimetric Mode"
  3. Start Dosing Unit
  4. Set P to Maximum Flow Rate
  5. Start Calibration Program "Vol. Discharge Adaption"
  6. Wait until Deviation is around zero and for control magnitude and set/act value to stabilize on display
  7. Press "Apply" - value will be taken over into Parameter P 12.03 Bypass

9.3.3 Adjust mechanical setup of the Vibro Feeder or modify P42.07 of VVC 29150 if determined Bypass value is too high[edit | edit source]

If for whatever reason the determined Bypass value after the Volumetric Discharge Adaption is outside of the recommended range of 10-12mA for dosings with low flow rate and 14mA for dosings with high flow rate, there are two possibilities to change that:

  1. Change mechanical setup of the Vibro feeder
  2. Adjust P42.07 Gain (Index) 1 of the VVC 29150: This value defines with which factor the system amplifies the actual value of the vibration amplitude. In other words, this value affects the maximum possible vibration amplitude – the higher the value, the higher the amplitude.

Note: This parameter only works in combination with the sensor VRS 20300 and only applies to the conveyor speed range 1.

9.3.4 Run Calibration programs "Linearization P1, P2, P3 and P4"[edit | edit source]

Note: The vibro feeder discharge characteristic is non-linear. To improve the assignment of set points to actual values and the control quality in gravimetric mode, linearization has to be performed.
Recommended values are: P1 = 5%, P2 = 10%, P3 = 30%, P4 = 60% of the Maximum Flow Rate

  1. View "Scale Operation 1" and start Keyboard Mode
  2. Set "Gravimetric Mode" and start Dosing Unit
  3. Enter feed rates P1 to P4 at P
  4. Open Calibration Programs
  5. Start Program Linearization P1
  6. Wait until deviation value is around zero
  7. Accept result by pressing apply
  8. Call up Linearization Program P2 and repeat previous steps (don’t forget to change P to P2)
  9. Call up Linearization Program P3 and repeat previous steps (don’t forget to change P to P3)
  10. Call up Linearization Program P4 and repeat previous steps (don’t forget to change P to P4)
  11. Set Parameter P 13.01 Linearization to YES
  12. Set setpoints P1 to P4 once more and check if actual feeding rate I reaches the setpoint P more smoothly

Template:Notice bms Finally please make sure that P12.19 Controller Adaptation is set to YES and the Dosing Unit is ready for a function test.

10 Replacement of FRS 0052 by VVC 29150 with Disocont Tersus[edit | edit source]

10.1 Installation[edit | edit source]

  1. Before you start make sure that all control voltages are off
  2. Disconnect all wires from the FRS 0052 – even those which are connected to the grey screw terminals
  3. Replace FRS 0052 controller by the VVC 29150
  4. Install RS 485 connection on terminals X103:7 and 8 at VVC 29150 and X97:5 and 4 at Disocont Tersus
  5. Set S301 according to the used sensor type and S401 to int
  6. Connect wires (power supply, sensor, exciter, etc.) at the VVC 29150 as follows:

Template:Image

Signal Terminal on FRS 0052 Terminal on VVC 29150
Digital input 1 (starts the feed operation) X2:10 X103:3
Digital input 2 (only relevant if the sensor VRS 20300 is connected) X3:4 X103:4
External reference potential for controlling the digital inputs 1 and 2 X2:6 X103:2
Analog setpoint (+) X2:1 X103:10
Analog setpoint (-) X2:2 X103:9
Digital relay output for feed control system (sends response "Ready" to the feed control system) X2:3 X501:2
Digital relay output for feed control system (sends response "Ready" to the feed control system) X2:5 X501:1
Ground of power supply PE PE
Power supply X1:L X801:5
Power supply X1:N X801:4
Exciter X1:+ X801:1
Exciter X1:- X801:2
Ground of exciter PE Screen clamp
Sensor X4:1 X301:1
Sensor X4:2 X301:2
Ground of sensor X4:3 Screen clamp


10.2 Firmwareupdate of Schenck Tersus Controller[edit | edit source]

Template:Notice bms#Start EasyServe v28

  1. Goto Tools / Flash / Flash SPI
  2. Choose your type of communication (Ethernet might be more convenient)
  3. Enter IP address
  4. Select firmware
  5. Follow instructions according to download manager

After the firmware download has been successfully finished you will recognize that the IP address as well as the name has been set to default values.

  1. Goto Connection / Ethernet (Scanner) - you will see the previously updated dosing unit shown as red
  2. Select the controller and hit the Configure button
  3. Type in the former IP address, subnetmask and gateway and click on Apply
  4. After that press the Configure button one more time and carry out the same procedure for the name of the dosing unit. Setting up name and IP address in one step somehow didn’t work during my test, but maybe you are luckier.

In case the firmware download for whatever reason fails and you cannot reach the dosing unit via Ethernet anymore you need to set up a serial connection to the unit via terminal X102:

Contact on X102 (VVC 29150) RS232 serial port on the PC
1 (GND) 5 (GND)
2 (Tx) 2 (Rx)
3 (Rx) 3 (Tx)








After that you should be able to carry out the firmware download one more time and hopefully finish it without any troubles.

10.3 Commissioning[edit | edit source]

The commissioning consists of four major steps:

  1. Check actual feeding rate I with current Bypass value
  2. Perform Calibration program “Vol. Discharge Adaption”
  3. Adjust mechanical setup of the Vibro Feeder or modify P42.07 of VVC 29150 if determined Bypass value is too high – recommended range 10-12mA for dosings with low flow rate and 14mA for dosings with high flow rate
  4. Run Calibration programs “Linearization P1, P2, P3 and P4”


10.3.1 Check actual feeding rate with VVC 29150[edit | edit source]

  1. Open EasyServe v28 (or higher) and connect to the dosing unit
  2. Unlock EasyServe user interface
  3. Enable Expert mode with pw 7353 (Edit / Expert Mode)
  4. Open Parameter Panel and set P01.16 Vibro Controller VVC to “YES” (VVC 29150 will be enabled)
  5. Set P12.21 Bypass Adaption if not already configured to 1,000 and deactivate P12.19 Controller Adaptation
  6. Open "Scale Operation 1" and start Keyboard Mode
  7. Enable Volumetric Mode and start the dosing unit
  8. Set P to Maximum Flow Rate

Template:Notice bms

10.3.2 Calibration program "Vol. Discharge Adaption"[edit | edit source]

  1. View "Scale Operation 1"
  2. Set "Gravimetric Mode"
  3. Start Dosing Unit
  4. Set P to Maximum Flow Rate
  5. Start Calibration Program "Vol. Discharge Adaption"
  6. Wait until Deviation is around zero and for control magnitude and set/act value to stabilize on display
  7. Press "Apply" - value will be taken over into Parameter P 12.03 Bypass

10.3.3 Adjust mechanical setup of the Vibro Feeder or modify VVC 29150 parametrization if determined Bypass value is too high[edit | edit source]

If for whatever reason the determined Bypass value after the Volumetric Discharge Adaption is outside of the recommended range (10-12mA for dosings with low flow rate and 14mA for dosings with high flow rate) there are two possibilities to change that:

  1. Change mechanical setup of the Vibro feeder
  2. Adjust P42.07 Gain (Index) 1 or P42.09 Oscillation Amplitude MESM of the VVC 29150:

Note: P42.07 only works in combination with sensor VRS 20300 and P42.09 only with VME 29150.
P42.07 defines with which factor the system amplifies the actual value of the vibration amplitude. In other words, this value affects the maximum possible vibration amplitude – the higher the value, the higer the amplitude.
P42.09 specifies the maximum vibration amplitude. By default this parameter is set to 1.5mm – adjustment range according to Schenck: 0.8 to 2.0mm

10.3.4 Run Calibration programs "Linearization P1, P2, P3 and P4"[edit | edit source]

Note: The vibro feeder discharge characteristic is non-linear. To improve the assignment of set points to actual values and the control quality in gravimetric mode, linearization has to be performed.
Recommended values are: P1 = 5%, P2 = 10%, P3 = 30%, P4 = 60% of the Maximum Flow Rate

  1. View "Scale Operation 1" and start Keyboard Mode
  2. Set "Gravimetric Mode" and start Dosing Unit
  3. Enter feed rates P1 to P4 at P
  4. Open Calibration Programs
  5. Start Program Linearization P1
  6. Wait until deviation value is around zero
  7. Accept result by pressing apply
  8. Call up Linearization Program P2 and repeat previous steps (don’t forget to change P to P2)
  9. Call up Linearization Program P3 and repeat previous steps (don’t forget to change P to P3)
  10. Call up Linearization Program P4 and repeat previous steps (don’t forget to change P to P4)
  11. Set Parameter P 13.01 Linearization to YES
  12. Set setpoints P1 to P4 once more and check if actual feeding rate I reaches the setpoint P more smoothly

Template:Notice bms Finally please make sure that P12.19 Controller Adaptation is set to YES and the Dosing Unit is ready for a function test.