The protocol is prepared in Siegsdorf so that it is matching for your line and only categories and sensor which exist on your line are mentioned.
Path to protocol: \\KOM\projects\KOM\_engineering\public\documents\machine_data\XXXX_KOM_checklist_utility_measurements-EEC.xlsx
Fill in the protocol while you commission the system. This way you will not forget anything and you have all the data available that you need for filling in the protocol (trends, set values etc.).
After you have filled in this protocol, commit it to the SVN and send it to Siegsdorf
The energy measurement system measures, how much energy is consumed in several categories. There exist sensors for each category that we have to commission, calibrate and verify during the check up. Not every line has all of the below mentioned categories. Follow the protocol in order to see, which categories exist on your line.
Water
PT100 temperature sensors (see section below)
Flow meters (see section below)
Oil
PT100 temperature sensors (see section below)
Flow meters (see section below)
Oil type
Get the used oil type from customer or site manager and select in the panel
What to do if sensors are not accessible, extra nozzles are missing or cables are too short for exchanging between supply and return line?
First, try to solve it on site together with the site manager.
If you cannot find a solution on site, take pictures and send an e-mail to Template:EEC-Support explaining the situation. If this issue gets reported repeatedly from many lines, we will try to improve the installation procedures.
First, perform the basic commissioning for each sensor. Make sure the assignment is correct and you get a proper value. Then perform the tasks described below for each sensor.
The first sections describes the calibration procedure for most of the measuring points at the line. The second section describes the calibration procedure for the Casting Unit Hybrid Cooling System.
4.1 Calibration at ordinary measuring points[edit | edit source]
There are no additional nozzels at the cooling units with hybrid-cooling.
In order to calibrate the sensors the line has to be stopped.
Close the manual valves at tower water and chilled water supply (to close control valves is not sufficient)
Open the trends of the three sensors and start the pump
All sensors should show the same temperature as they are in the same line and there is no cooling or heating in between
If not, put an offset as described above. Do not enter the offset into the datapoint which is used for the controller (StrCas.Tmp*Ctl). Instead enter the offset in one of the other sensors marked in red on the screenshot above.
Check that the value shown on the display of the flow meter is matching with the value in WinCC.
If not, then the value for 20mA at the flow meter is not matching with the range set in the WinCC parameters.
Check that the serial number of the transmitters is matching with the serial number of the receiver.
The flow meter consists of a transmitter and a receiver. Each receiver can only show correct results, when connected to the dedicated transmitter. Therefore check that the serial number of the transmitters is matching with the serial number for the receiver. If the serial number is not matching, the transmitter-receiver pairs were probably mixed up during installation. Look for the matching partner at other positions along the line.
The sensors are set to the values from the BMS Mat.-Nr. specification by the subsupplier but we need to check if the measuring range is big enough.
If the measuring range is exceeded (i.e. output signal > 20 mA) there is an error message on the display and in WinCC (currently alarm max, in future sensor fault). In that case, expand the measuring range at the sensor and in WinCC.
The measuring range should be at least 20% larger than the expected flow.
The extended measuring range should not be identical to the standard measuring range of the next larger sensor (so that you can immediately see that the measuring range was intentionally extended here and not just by mistake that an incorrect measuring range was entered).
Follow the instructions in the article for the specific device linked below for changing the measuring range.
After changing the measuring range, write the new values into the PROTOCOL.
Water
Details for the water flow meter can be found here Promag .
Oil
Check whether the flow meter is installed in the supply or in the return line
There is the Bit StrGnl.OilFlwSenRtuPos.Bit in StrGnl.SCL together with a Checkup comment.
Check if the flow meter is installed in supply or return line, set the Bit accordingly and resolve the Checkup comment.
Write into PROTOCOL.
On most lines we are using the Prowirl flow meter. In some cases however we are using the old setup with the orifice.