YM:Festo MS6 - electrical connection: Difference between revisions

hw>Fkb
Text replacement - "<bs:bookshelf src="Book:Book Public" />" to ""
 
m 1 revision imported
 
(No difference)

Latest revision as of 10:52, 9 March 2026




Template:Infobox bms


File:Festo MS6 Original Festo Drawings.jpg
The original Festo drawing

File:Festo MS6 Patch Festo Drawings.jpg
Modify the connection like this drawing. Take care to modify the connector labels

Description:

  • Open Plug connector at MS6
  • Disconnect the wire at Terminal 4 and connect it to Terminal 5
  • Change Terminal Labels in the Cabinet like in the modified drawing (303 -> 302, ...)
  • Make sure that the wires from BMS side are connected right
  • Check that the Terminal 306 and 307 are jumpered (Automatic Start mode of MS6 Valve)
  • Remove other Jumpers, which are not needed! Festo put sometimes for all 24V, but BMS supply the devices from the IO card.
File:Festo MS6 Patch BMS Drawing.jpg
BMS Drawing